Figure 5-14
Lug Installation
Note:
Input Power and RTN use straight, two hole lugs, 1/4-inch hole on 5/8-inch
centers, long barrel with window (P/N 804-0817-02).
Double crimp the lugs onto the cable end using the embossing crimper.
7.
Slide the one-inch length of clear tubing over the crimped lug and heat-shrink the one-
8.
inch length of clear tubing.
Fasten the lugs of the cables to the respective A-side and B-side -48VDC and RTN
9.
points on the FAP. Refer to
Figure 5-15
1U Fuse and Alarm Panel Rear (P/N 870-2804-01)
Figure 5-16
3U Fuse and Alarm Panel Rear (P/N 870-2320-03))
Figure 5-15
and
Figure
5-16.