channel 00-05-31 06:10:29 EST Rel XX.X.X-XX.X.X
CHG-SECU-TRM: MASP A - COMPLTD
Issue the command to set the system monitoring feature for the terminal you are logged
6.
into.
> chg-trm:all=no:sys=yes:trm=1
Command Accepted - Processing
tekelecstp 12-12-23 08:52:15 EST Rel XX.X.X-XX.X.X
chg-trm:all=no:sys=no:trm=1
Command entered at terminal #1.
;
tekelecstp 12-12-23 08:52:16 EST Rel XX.X.X-XX.X.X
CHG-TRM: MASP A - COMPLTD
Remove a fuse from the first position of A-side fuse bank on the FAP and insert a blown
7.
fuse in its place. This will be done on the A-side then the B-side of the FAP
The FUSE ALM LED for that side and the Major LED should illuminate RED after the
blown fuse has been inserted indicating the presence of a blown fuse.
The VT terminal of the STP should report the presence of a blown fuse.
8.
Tekelecstp 00-05-31 11:18:42 EST Rel XX.X.X-XX.X.X
**
5050.0082 ** FUSE PANEL 11xx
Enter the command to display the system alarms.
9.
> rept-stat-trbl
The following command response is displayed.
10.
Verify that the alarm condition appears in the rept-stat-trbl screen.
Command Accepted - Processing
tekelecstp 00-05-31 11:15:38 EST Rel XX.X.X-XX.X.X
rept-stat-trbl
Command entered at terminal #1.
;
tekelecstp 00-05-31 11:15:38 EST Rel XX.X.X-XX.X.X
Searching devices for alarms...
;
tekelecstp 00-05-31 11:15:38 EST Rel XX.X.X-XX.X.X
SEQN UAM
AL
5012.0048
*
5014.0048
*
5016.0048
*
5042.0082
** FUSE PANEL 11xx
5043.0308
*C SYSTEM
failures
Command Completed.
Alarm in Fuse Panel
DEVICE
ELEMENT
TERMINAL
2
Terminal failed
TERMINAL
3
Terminal failed
TERMINAL
4
Terminal failed
Alarm in Fuse Panel
Node isolated due to SLK
FAP Alarm System Test
TROUBLE TEXT