Oracle Private Cloud Appliance Quick Start Guide
C
Appliance Components
D
ZFS Storage Appliance
A
Management Nodes (2)
F
B
E
Compute Nodes (up to 25)
C
F1-15 Fabric Interconnects (2)
D
D
NM2-36P In niBand Switches (2)
E
ES1-24 Ethernet Switch A | B
F
C
B
A
Verify Installation Requirements
Space Requirements
Receiving and unpacking:
Maintenance clearance:
A
B
Packaged Base Rack
Fully Populated
with Shipping Pallet
Base Rack
Rear maintenance
Height
2159mm (85 in)
1998mm (78.66 in)
Front Maintenance
1219mm (48 in)
600mm (23.62 in)
Width
Top Maintenance
Depth
1575mm (62 in)
1200mm (47.24 in)
Side panel removal
Weight
996kg (2197 lbs)
894kg (1972 lbs)
Note: Allow enough space to remove the shipping cartons. The minimum required depth
for roll-off is 4.5m (15ft). Refer to the Sun Rack II Unpacking Guide (820-5210) included with
the packaging for further details.
Access route to installation site:
C
With Shipping Pallet
Without Shipping Pallet
Minimum door height
2184mm (86 in)
2040mm (80.32 in)
1220mm (48 in)
600mm (23.62 in)
Minimum door width
Minimum elevator depth
1575mm (62 in)
1200mm (47.24 in)
Maximum incline
6 degrees
6 degrees
Loading capacity (elevator,
1134kg (2500 lbs)
1134kg (2500 lbs)
pallet jack, oor)
Data Center Con guration
Oracle recommends using raised ooring, able to support the total weight
A
of the system including power distribution units (PDUs): 1005kg (2215lbs).
Temperature, humidity and altitude:
B
Operating
Requirement
Temperature
5°C to 32°
(41°F to 89.6°F)
Relative
10-90 percent,
non-condensing
humidity
3048m (10000ft)
Altitude
maximum
Provide adequate ventilation and cooling:
C
• Make sure that the capacity of the air conditioning equipment is suf cient
for the new system hardware.
• Respect the maintenance clearance at the front and back of the system for
optimum air ow. The air intake is at the front, and the air outlet is at the
back.
• Install perforated oor tiles (approximately 400 CFM/tile) in front of the
rack for cold air intake. Use four tiles for a fully populated
rack, three tiles for 8-16 compute nodes, or one
tile for 8 or fewer compute nodes.
Access Requirement
• Cover empty rack units with ller
914mm (36 in)
panels to avoid adverse effects
914mm (36 in)
on air ow and cooling.
914mm (36 in)
676mm (26.6 in)
(part 1)
Non-operating
Optimum
Requirement
-40°C to 70°C
21°C to 23°C
(-40°F to 158°F)
(70°F to 74°F)
93 percent
45-50 percent, non-condensing
maximum
12000m
ambient temperature is reduced by 1°C per
(40000ft)
300m above 900m altitude above sea level
Power Requirements
Each rack has two preinstalled power distribution units (PDUs). The PDUs accept different
power sources. You must specify the type of PDU that is correct for your data center.
Verify that the PDUs installed are correct for your data center power source: 22 or 24kVA for
A
low or high voltage.
PDU power cords are 4m (13.1ft) long, and up to 1.5m (4.9ft) is routed within the rack cabinet.
B
AC power receptacles must be within 2m (6.6ft) of the rack.
Use dedicated AC breaker panels for all power circuits that supply power to the PDU.
C
Use dedicated AC breaker panels for all power circuits that supply power to the compute nodes.
D
Compute nodes require electrical circuits to be grounded to the Earth.
Note: Circuit breakers are supplied by the customer. One circuit breaker is required for each power cord.
In addition to circuit breakers, provide a stable power source, such as an uninterruptable power
E
supply (UPS) to reduce the possibility of component failures.
Racks are shipped with grounding-type power cords (three-wire). Always connect the cords to
F
grounded power outlets. Verify the correct grounding method for your location.
Network Requirements
Four ports (2x2) on redundant next-layer switches in the data center must be reserved
A
to connect the 10GbE public network ports of the Fabric Interconnects.
A terminal or workstation with a web browser must be connected to the management network.
B
Three IP addresses in the public network must be reserved for management node con guration.
C
The following network con guration details are required:
D
Your Entry
Description
Domain Name
Data center network
Region and Time Zone
Location and time zone where the system is installed
IP address of one to three Domain Name Servers
DNS IP address
NTP server IP address
IP address of your Network Time Protocol server
Default Gateway
IP address of the default gateway in your data center network
IP address of the rst management node in your
Management Node 1
data center network
IP address of the second management node in your
Management Node 2
data center network
IP address providing access to the master management node
Management Virtual IP
Management VLAN
VLAN ID of the management network, if applicable
Note: All internal rack connections are pre-cabled, including non-populated rack units. Cabling should not be
modi ed in any way.
1

Advertisement

loading

Summary of Contents for Oracle E71887

  • Page 1 Data Center Con guration Power Requirements Oracle recommends using raised ooring, able to support the total weight Each rack has two preinstalled power distribution units (PDUs). The PDUs accept different of the system including power distribution units (PDUs): 1005kg (2215lbs).
  • Page 2 Copyright © 2013-2016, Oracle and/or its affiliates. All rights reserved. Oracle and Java are registered trademarks of Oracle and/or its affiliates. Other names may be trademarks of their respective owners. Document part no.: E71887-01. Mfg. no.: 7329825.
  • Page 3 IP address 192.168.4.254. • Check the airflow that leads in to the front of the Note: For advanced network con guration options, refer to the Oracle system. (See Verify Installation Requirements.) • Secure the power cords in bundles.
  • Page 4 Note: You cannot obtain software or support from Oracle without registered hardware and software SIs. Copyright © 2013-2016, Oracle and/or its affiliates. All rights reserved. Oracle and Java are registered trademarks of Oracle and/or its affiliates. Other names may be trademarks of their respective owners. Document part no.: E71888-01. Mfg. no.: 7329826.