Oracle EAGLE Installation Manual page 72

Table of Contents

Advertisement

Figure 5-4
Pull the board straight out of the FAP until the board is clear of the frame.
3.
Turn the Shorting Board over and reinsert the board into its slot. Note the
4.
orientation of the Shorting Board LED (see
Figure 5-5
The Shorting Board LED turns green and the fuse alarm LEDs turn red.
Ensure the board is seated properly and tighten the two screws to secure the
5.
board.
The Shorting Board is now in the maintenance (bypass) mode of operation.
6.
5.1.2.1.2 Normal Mode
Use this procedure to place the Shorting board into normal mode. This mode of
operation allows one bus to pick up the entire load when there is a loss of input power
on the other bus.
Procedure — Shorting Board Normal Mode
Check to verify the Shorting Board LED is green, indicating the FAP is in
1.
maintenance mode.
Locate two screws securing the Shorting Board in its slot. Note the orientation of
2.
the Shorting Board LED
to the left until they disengage.
Figure 5-6
Pull the board straight out of the FAP until the board is clear of the frame.
3.
Turn the Shorting Board over and reinsert the board into its slot. Note the
4.
orientation of the Shorting Board LED (see
Shorting Board Faceplate, Normal Mode
Shorting Board Faceplate, Maintenance Mode
(Figure
5-6). Turn the screws at each corner of the board
Shorting Board Faceplate, Maintenance Mode
Fuse and Alarm Panels
Figure
5-5).
Figure
5-7).
Chapter 5
5-6