4276.0161
* CLOCK SYSTEM
Legend: minor (*), major (**), critical (C*), and inhibited (I)
alarms.
Caution:
If Both PRIMARY BITS and SECONDARY BITS clocks show FAULT
condition, reconnect the cable (P/N 830‑0226‑xx) to the appropriate
connector (J48 or J49) and abort this procedure. Contact the
Support (MOS)
If you check the system for clock alarms, the output will show clock errors; enter:
16.
rept-stat-trbl
The output will show any minor (*), major (**), critical (C*), and inhibited (I) alarms.
The following display shows possible error messages with their alarm indicators:
* 0014.0021 *
CARD 1116 OAM Clock A for card failed, Clock B
normal
* 0014.0022 *
CARD 1116 OAM Clock B for card failed, Clock A
normal
* 0014.0023 *
CARD 1116 OAM Clocks A and B for card failed
**0046.0023
* CARD 1201 ATMANSI Clocks A and B for card failed
**4307.0164 ** CLOCK SYSTEM 1114-P, 1116-P clocks failed
Legend: minor (*), major (**), critical (C*), and inhibited (I)
alarms.
At the output panel of the customer composite clock source, locate the end of the
17.
composite/BITS clock cable (P/N 830‑0226‑xx) that was disconnected in
remove all wires.
Connect the new high‑speed source clock and composite cable (P/N 830‑0873‑xx
18.
or P/N 830‑1189‑xx) to the site HS clock source.
Cut the wires to length and strip.
a.
Wire‑wrap to the appropriate IDLE (primary or secondary) clock connections
b.
on the customer clock source. Refer to the cable wire coding (P/
N 830‑0873‑xx or P/N 830‑1189‑xx) shown in
information.
Connect the HS clock source to the orange and white/orange wires.
Connect the composite clock source to the blue and white/blue wires.
1116-P clock failed
for assistance.
Source Timing
My Oracle
15
Figure 6-32
for connection
Chapter 6
and
6-68