Cables And Adapters; Labeling Cables; Procedure - Cable Labeling - Oracle EAGLE Installation Manual

Table of Contents

Advertisement

C

Cables and Adapters

C.1 Labeling Cables
This section provides general labeling instructions for cables.
Before installing any cable use this procedure to label the cables to ensure connection to the
proper ports and ease of future maintenance.
warning:
The intra-building port(s) of the equipment or subassembly is suitable for
connection to intra-building or unexposed wiring or cabling only. The intra-building
port(s) of the equipment or subassembly MUST NOT be metallically connected to
interfaces that connect to the Outside Plant (OSP) or its wiring. These interfaces
are designed for use as intra-building interfaces only (Type 2 or Type 4 ports as
described in GR-1089-CORE, Issue 4) and require isolation from the exposed OSP
cabling. The addition of Primary Protectors is not sufficient protection in order to
connect these interfaces metallically to OSP wiring.
Recommended Tools
Installer's Cable Running List
All cables listed in Installer's Cable Running List
Any non-Oracle cables
Cable labels (including blank labels for non-Oracle cables)
Fine point marker
C.1.1 Procedure - Cable Labeling
Perform this procedure to label cables.
Locate the Installer's Cable Running List in the Equipment Specification for the site.
1.
Refer to
Figure C-1
for an example.