The fuse card located on the Fuse and Alarm Panel are marked FAN A and FAN B,
fuse positions 6, 12, and 18 are marked correct locations on the FAP faceplate.
Fuse position 6 is for the fan unit directly below the x100 shelf.
Fuse position 12 is for the fan directly below the x200 shelf.
Fuse position 18 is for the fan directly below the x300 shelf.
All fans are to be fused at 3As, with blue flags, per feed.
Fill out the fuse card completely.
Ensure the FAP fuse location for the fan is properly labeled.
Fifteen seconds after both the A side and B side power is connected to the fan assembly
2.
all of the LEDs on the fan controller card (located on the left side of the front of the fan
assembly) are green.
Figure 6-23
Fan card with LEDs on front of fan assembly
When the fans are powered up and running, a test must be conducted to ensure proper
3.
service.
Go to the system terminal.
Check to see if the fan feature is activated. At the terminal, enter the command:
4.
rtrv-feat
If the fan feature is off, go to 5. Otherwise, go to 6.
At the terminal, enter the command:
5.
chg-feat:fan=on
Note:
UAM 0080 will be raised for HC-MIM, E5-EPM-B or E5-SM8G-B if shelf FAN bit
is OFF. These cards can be provisioned with ent-cardcommand. UAM 0080
will be cleared once shelf FAN bit is turned ON.
Chapter 6
Fan Assembly Installation and Cabling
6-43