GD310-UL series VFD
Function
Name
code
Delay time of
P01.24
the stop speed
0Hz output
P01.25
selection
P02 Group Motor 1
Function
Name
code
Motor type 1
P02.00
Rated power
P02.01
of AM 1
Rated
frequency of
P02.02
AM 1
Rated speed
P02.03
of AM 1
Rated voltage
P02.04
of AM 1
Rated current
P02.05
of AM 1
Stator resistor
P02.06
of AM 1
Rotor resistor
P02.07
of AM 1
Leakage
inductance of
P02.08
AM 1
Mutual
inductance of
P02.09
AM 1
Non-load
P02.10
current of AM 1
stand-by state and wait for the delay time set by
P01.23
Setting range: 0.0–60.0s
Setting range: 0.0–100.0 s
Select the output mode at 0Hz.
0: Output without voltage
1: Output with voltage
2: Output at DC braking current at stopping
0: Asynchronous motor
1: Synchronous motor
Note: Switch the current motor by the switching
channel of P08.31.
0.1–3000.0kW
0.01Hz–P00.03 (the max frequency)
1–36000rpm
0–1200V
0.8–6000.0A
0.001–65.535Ω
0.001–65.535Ω
0.1–6553.5mH
0.1–6553.5mH
0.1–6553.5A
Description
Description
-51-
Function parameter
Default
Modify
value
○
0.0s
○
0
Default
Modify
value
◎
0
Depend
◎
on model
◎
60.00Hz
◎
◎
◎
○
Depend
○
on model
○
○
○
Need help?