GD310-UL series VFD
Function
Name
code
Multi-step
P10.20
speed 9
Running time
P10.21
of step 9
Multi-step
P10.22
speed 10
Running time
P10.23
of step 10
Multi-step
P10.24
speed 11
Running time
P10.25
of step 11
Multi-step
P10.26
speed 12
Running time
P10.27
of step 12
Multi-step
P10.28
speed 13
Running time
P10.29
of step 13
Multi-step
P10.30
speed 14
Running time
P10.31
of step 14
Multi-step
P10.32
speed 15
Running time
P10.33
of step 15
Simple PLC
0–7 step
P10.34
ACC/DEC
time
Simple PLC
8–15 step
P10.35
ACC/DEC
time
When terminal 1, terminal 2, terminal 3, terminal
4=OFF, the frequency input manner is selected via
code P00.06 or P00.07. When terminal 1, terminal 2,
terminal 3, terminal 4 aren't off, it runs at multi-step
which takes precedence of keypad, analog value,
high-speed pulse, PLC, communication frequency
input.
The relationship between terminal 1, terminal 2,
terminal 3, terminal 4 and multi-step speed is as
following:
Terminal 1 OFF ON OFF ON OFF ON OFF ON
Terminal 2 OFF OFF ON ON OFF OFF ON ON
Terminal 3 OFF OFF OFF OFF ON ON ON ON
Terminal 4 OFF OFF OFF OFF OFF OFF OFF OFF
Step
0
1
Terminal 1 OFF ON OFF ON OFF ON OFF ON
Terminal 2 OFF OFF ON ON OFF OFF ON ON
Terminal 3 OFF OFF OFF OFF ON ON ON ON
Terminal 4 ON ON ON ON ON ON ON ON
Step
8
9
Below is the detailed instruction:
Function
Binary bit
code
BIT1
BIT0
BIT3
BIT2
BIT5
BIT4
BIT7
BIT6
P10.34
BIT9
BIT8
BIT11 BIT10
BIT13 BIT12
BIT15 BIT14
Description
2
3
4
5
10
11
12
13
ACC/
ACC/
ACC/
Step
DEC 0
DEC 1
DEC 2
0
00
01
1
00
01
2
00
01
3
00
01
4
00
01
5
00
01
6
00
01
7
00
01
-94-
Function parameter
Default
value
0.0%
0.0s
0.0%
0.0s
0.0%
0.0s
0.0%
0.0s
6
7
0.0%
0.0s
0.0%
14
15
0.0s
0.0%
0.0s
ACC/
0x0000
DEC 3
10
11
10
11
10
11
10
11
10
11
0x0000
10
11
10
11
10
11
Modify
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
Need help?
Do you have a question about the Goodrive 310-UL Series and is the answer not in the manual?