GD310-UL series VFD
Function
Name
code
Hibernation
P01.20
restore delay
time
Restart after
P01.21
power off
The waiting
P01.22
time of restart
after power off
Start delay
P01.23
time
This function code determines the hibernation delay
time. When the running frequency of the VFD is
lower than the lower limit one, the VFD will pause to
stand by.
When the set frequency is above the lower limit one
again and it lasts for the time set by P01.20, the VFD
will run automatically.
Note: The time is the total value when the set
frequency is above the lower limit one.
t1 < P01.20, the VFD does not run
Frequency f
t1+t2 ≥P01.20, the VFD runs
t0=P01.34, sleep delay
Frequency lower
limit f0
t0
Run
Coast to
stop
Setting range: 0.0–3600.0s (valid when P01.19=2)
This function can enable the VFD start or not after
the power off and then power on.
0: Disable
1: Enable, if the starting need is met, the VFD will run
automatically after waiting for the time defined by
P01.22.
The function determines the waiting time before the
automatic running of the VFD when powering off and
then powering on.
Output frequency
Running
Power off
Setting range: 0.0–3600.0s (valid when P01.21=1)
The function determines the brake release after the
running command is given, and the VFD is in a
Description
Set frequency curve:
Running frequency curve:
t2
t1
Run
Sleep
=
t1=P01.22
=
t2=P01.23
t1
t2
Running
Power on
-50-
Function parameter
Default
Modify
value
0.0s
Time t
0
1.0s
t
0.0s
○
○
○
○