GD310-UL series VFD
Function
Name
code
P15.13 PZD2 sending 0: Invalid
P15.14 PZD3 sending
P15.15 PZD4 sending
P15.16 PZD5 sending
P15.17 PZD6 sending
P15.18 PZD7 sending
P15.19 PZD8 sending
P15.20 PZD9 sending
PZD10
P15.21
sending
PZD11
P15.22
sending
PZD12
P15.23
sending
Temporarily
P15.24
variable 1 for
PZD sending
Fault time of
DP
P15.25
communica
-tion overtime
corresponds to 100.0%)
13: AO output set value 2 (-1000–1000, 1000
corresponds to 100.0%)
14–20: Reserved
1: Running frequency (*100, Hz)
2: Setting frequency (*100, Hz)
3: Bus voltage (*10, V)
4: Output voltage (*1, V)
5: Output current (*10, A)
6: Output torque actual value (*10, %)
7: Output power actual value (*10, %)
8: Running rotating speed (*1, RPM)
9: Running linear speed (*1, m/s)
10: Ramp given frequency
11: Fault code
12: AI1 value (*100, V)
13: AI2 value (*100, V)
14: AI3 value (*100, V)
15: PULSE frequency value (*100, kHz)
16: Terminals input state
17: Terminals output state
18: PID given (*100, %)
19: PID feedback (*100, %)
20: Motor rated torque
21: Control word
0–65535
0.0 (invalid), 0.1–60.0s
When this function code is set as 0.0, this function is
invalid.
When the function code is set as nonzero value, if
the
internal
time
communication
exceeds
overtime,
the
system
communication fault" (E-DP).
Description
between
two
the
communication
will
report
-109-
Function parameter
Default
value
0
0
0
0
0
0
0
0
0
0
0
0
0.0s
adjacent
"PROFIBUS
Modify
○
○
○
○
○
○
○
○
○
○
○
○
○
Need help?
Do you have a question about the Goodrive 310-UL Series and is the answer not in the manual?
Questions and answers