GD310-UL series VFD
Fault
Fault type
code
[27] Parameter
UPE
uploading fault
[28] Parameter
DNE
downloading
fault
[29] PROFIBUS
E-DP
communication
fault
[30] Ethernet
E-NET
communication
fault
[31] CANopen
E-CAN
communication
fault
[32] To-ground
ETH1
short-circuit
fault 1
Cause
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
Communication fault.
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
There is mistake on the data
storage of the keypad.
Communication address is
not correct.
Corresponding resistor is
not dialed
The files of main stop GSD
does not set sound
The Ethernet address is not
set right.
The Ethernet
communication is not
selected to right.
The ambient interference is
too strong.
The connection is not sound
Corresponding resistor is
not dialed
The communication is
uneven
The output of the VFD is
short circuited with the
ground.
There is fault in the current
detection circuit.
-176-
Solution
Check the keypad wires and
ensure whether there is mistake.
Change the hardware and ask for
service.
Change the hardware and ask for
service.
Check the keypad wires and
ensure whether there is mistake.
Change the hardware and ask for
service.
Repack-up the data in the
keypad.
Check related setting
Check the related setting. Check
the communication method
selection.
Check the environment and avoid
the interference.
Check the connection
Draw out the correspond resistor
Set the same baud rate
Check if the connection of the
motor is normal or not
Change the hall
Change the main control panel
Fault tracking