GD310-UL series VFD
Function
Name
code
Energy
P08.37
braking enable
Threshold
P08.38
voltage
Cooling fan
P08.39
running mode
PWM
P08.40
selection
Output frequency
The set
frequency
,
Y
RO1, RO2
The setting range: 0.00Hz–P00.03 (the max
frequency)
This parameter is used to control the internal braking
pipe inside the VFD.
0: Disable
1: Enable
Note: Only applied to internal braking pipe.
After setting the original bus voltage to brake the
energy, adjust the voltage appropriately to brake the
load. The factory changes with the voltage level.
The setting range: 200.0–2000.0V
In order to prevent customers set the value is too
large, it is recommended setting range:
Voltage
220V
Range
360-390V 715–780V
0: Normal mode
1: The fan keeps running after power on
0x00–0x21
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
LED tens: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at low
speed
1: Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at low
speed
2: No limit
Description
Detecting
range
T
T
460V
950-1050V
-85-
Function parameter
Default
value
0
220V
voltage:
380.0V
460V
voltage:
740.0V
575V
575V
voltage:
1000.0V
0
01