P12 Group Motor 2 - INVT Goodrive 310-UL Series Operation Manual

Table of Contents

Advertisement

GD310-UL series VFD
Function
Name
code
Output
P11.13
terminal action
during fault
Speed
P11.14
deviation
detection
Speed
P11.15
deviation
detection time
Automatic
frequency-dec
P11.16
reasing at
voltage drop

P12 Group Motor 2

Function
Name
code
P12.00
Motor type 2
Rated power
of
P12.01
asynchronous
motor 2
Select the action of fault output terminals on
undervoltage and fault reset.
0x00–0x11
LED ones:
0: Action under fault undervoltage
1: No action under fault undervoltage
LED tens:
0: Action during the automatic reset
1: No action during the automatic reset
0.0–50.0%
Set the speed deviation detection time.
This parameter is used to see the speed deviation
detection time.
Actual detection
value
The set detection
value
t1<t2, so the inverter continues to work
t2=P11.15
Setting range of P11.15: 0.0–10.0s
0: Invalid
1: Valid; ensure rated output torque when voltage
drop
0: Asynchronous motor
1: Synchronous motor
Note: Switch the current motor by the switching
channel of P08.31.
0.1–3000.0kW
Description
Speed
t1
t2
In running
Fault output
Description
Set the parameter of the
controlled asynchronous
motor.
In order to ensure the
-99-
Function parameter
Default
value
0x00
10.0%
0.5s
dEu
0
Default
value
0
Depend
on model
Modify
Modify