Function
Name
code
Overmodulatio
P08.41
n selection
Keypad data
P08.42
control
Integral ratio
P08.43
of the keypad
potentiometer
UP/DOWN
P08.44
terminals
control
LED ones
0: Invalid
1: Valid
LED tens (for factory commissioning)
0: Light overmodulation; in zone 1
1: Heavy overmodulation; in zone 2
0x000–0x1223
LED ones: frequency enable selection
0: Both ∧ / ∨
keys and digital potentiometer
adjustments are valid
1: Only ∧/∨ keys adjustment is valid
2: Only digital potentiometer adjustments is valid
3: Neither ∧ / ∨ keys nor digital potentiometer
adjustments are valid
LED tens: frequency control selection
0: Only valid when P00.06=0 or P00.07=0
1: Valid for all frequency setting manner
2: Invalid for multi-step speed when multi-step speed
has the priority
LED hundreds: action selection during stopping
0: Setting is valid
1: Valid during running, cleared after stopping
2: Valid during running, cleared after receiving the
stop command
LED thousands: ∧/∨ keys and digital
potentiometer integral function
0: The integral function is valid
1: The integral function is invalid
0.01–10.00s
0x000–0x221
LED ones: frequency control selection
0: UP/DOWN terminals setting valid
1: UP/DOWN terminals setting valid
LED tens: frequency control selection
0: Only valid when P00.06=0 or P00.07=0
1: All frequency means are valid
Description
-86-
Function parameter
Default
Modify
value
◎
01
○
0x0000
○
0.10s
○
0x000
Need help?
Do you have a question about the Goodrive 310-UL Series and is the answer not in the manual?
Questions and answers