7.11 Digital input

Goodrive310-UL series VFDs have 8 programmable digital input terminals and 1 open circuit
electrode output terminal in the standard configuration. All functions of the digital input terminals are
programmable by the function codes. Open collector pole input can be selected into high speed pulse
input terminal or common switch input terminal by function code. When selected into HDI, the user
can select HDI high speed pulse input as frequency given, counting input or length pulse input by
setting.
P05.10
0
S1
1 -1
0
S2
1 -1
0
S3
1 -1
0
S4
1 -1
0
S5
1 -1
0
S6
1 -1
0
S7
1 -1
P05.00
0
S8
1 -1
0
0
1
HD1
1 -1
0
No function
4
Forward jogging
8
Running pause
Frequency increasing/decreasing
12
setting clear
16
Multi-stage speed terminal 1
20
Multi-stage speed pause
23
Simple PLC pause
28
Counter reset
32
Length reset
36
Shift the command to the keypad
40
Power consumption clear
This parameter is used to set the function corresponds to the digital multi-function terminals.
Note: two different multi-function terminals cannot be set as one function.
Set
Function
value
No function
0
Forward running (FWD)
1
2
Reverse running (REV)
3
3-wire running control
P05.11
P05.14
T delay
P05.16
T delay
P05.18
T delay
P05.20
T delay
P05.22
T delay
P05.24
T delay
P05.26
T delay
P05.28
T delay
P05.30
T delay
1
Forward running
5
Reverse jogging
9
External fault input
10
Shifting between A frequency and
13
14
B frequency
17
Multi-stage speed terminal 2
18
21
ACC/DEC time selection 1
22
25
PID control pause
26
29
Torque control disabling
30
Frequency increasing/decreasing
33
34
setting clear
37
Shift the command to the terminal
38
41
Power consumption keeping
42~63
The VFD does not work even there is input signal. It is
necessary to set the terminal which cannot be used to
non-function to avoid misacting.
The forward or reverse rotation of the VFD can be controlled
by the external terminals.
The terminal can determine the running mode of the VFD is
3-wire control mode. Refer to P05.13 for detailed instruction
of 3-wire control mode.
Switch function selection
P05.15
T delay
(default value is 1)
P05.17
T delay
(default value is 4)
P05.19
T delay
(default value is 7)
P05.21
T delay
(default value is 0)
P05.23
T delay
(default value is 0)
P05.25
T delay
(default value is 0)
P05.27
T delay
(default value is 0)
P05.29
T delay
(default value is 0)
P05.31
T delay
(default value is 0)
2
Reverse running
3
6
Coast to stop
7
Frequency setting increasing (UP)
11
Shifting between the combination
15
setting and A frequency
19
Multi-stage speed terminal 3
ACC/DEC time selection 2
23
Traverse pause (stop at the current
27
frequency)
31
ACC/DEC disabling
DC braking
35
Shift the command to the
39
communication
Reserved
Instructions
-147-
Basic operation instruction
0
P05.01
1
2
P05.02
Fault?
3
P05.03
4
P05.04
5
P05.05
.
P05.10, P17.12, P07.39 display
S1
.
P05.06
S3
S5
.
S7
P05.07
HDI
.
P05.00
P05.08
29
P05.09
30
3-wire running control
Fault reset
Frequency setting decreasing (DOWN)
Shifting between the combination setting
and B frequency
Multi-stage speed terminal 4
Simple PLC stopping reset
Traverse reset (stop at the middle
frequency)
Counter trigging
Shift from motor 1 to motor 2
Pre-exciting command
Running
P17.12
Digital input
terminals state
P07.39
Fault
Input terminals
state at present
fault
BIT0
S2
BIT1
BIT2
S4
BIT3
BIT4
S6
BIT5
BIT6
S8
BIT7
BIT8
0: HDI is high speed pulse
input
1: HDI is switch input