GD310-UL series VFD
Function
Name
code
Correction
P12.28
coefficient of
motor 2 power
Parameter
P12.29
display of
motor 2
P13 Group Synchronous motor control
Function
Name
code
Reduction
P13.00
coefficient of
source current
Original pole
P13.01
test mode
Source current
P13.02
1
of M is. When M =116%, the fault will be reported
after 1 hour, when M =200%, the fault will be
reported after 1 minute, when M>=400%, the fault
will be reported instantly.
Setting range: 20.0%–120.0%
Correct the power displaying of motor 2.
Only impact the displaying value other than the
control performance of the VFD.
Setting range: 0.00–3.00
0: Display according to the motor type: only the
parameters relative to the current motor type are
displayed for the convenient for the customers in this
mode.
1: All parameters are displayed: all parameters are
displayed in this mode.
0.0–100.0%
0: No test
1: High-frequency superposition (reserved)
2: Pulse superposition
Source current is the positioning current of the
magnetic pole position. Source current 1 is valid
under the frequency point of current shifting.
Increasing the value can raise the starting torque.
Setting range: 0.0%–100.0% (rated current of the
motor)
Description
Description
-104-
Function parameter
Default
Modify
value
○
1.00
○
0
Default
Modify
value
◎
80.0%
◎
0
○
20.0%
Need help?
Do you have a question about the Goodrive 310-UL Series and is the answer not in the manual?
Questions and answers