Fine Tuning During Test Runs (Adjust The Control Function); V/F Control - YASKAWA GA500 GA50U Series Programming Manual

Table of Contents

Advertisement

3.7
Fine Tuning during Test Runs (Adjust the Control
Function)
This section gives information about the adjustment procedures to stop hunting or oscillation errors caused by the
control function during a test run. Adjust the applicable parameters as specified by your control method and drive
status.
V/f Control on page 481
Open Loop Vector Control for PM Motors on page 484
Advanced Open Loop Vector Control Method for PM Motors on page 485
EZ Open Loop Vector Control Method on page 485
Note:
This section only lists frequently adjusted parameters. If you must adjust parameters that have a higher degree of precision, contact Yaskawa.

V/f Control

Issue
Hunting or oscillation at mid-range
n1-02 [Hunting Prevention Gain
speeds (10 Hz to 40 Hz)
Setting]
• The volume of the motor
excitation sound is too high.
C6-02 [Carrier Frequency
• Hunting or oscillation at low
Selection]
speeds (10 Hz or lower), or at
mid-range speeds (10 Hz to 40
Hz)
• Unsatisfactory motor torque
C4-02 [Torque Compensation
and speed response
Delay Time]
• Hunting or oscillation
• Torque at low speeds (10 Hz or
C4-01 [Torque Compensation
lower) is not sufficient.
Gain]
• Hunting or oscillation
• If you use the drive with an IE3
high efficiency motor, the
current that is more than the
C4-01 [Torque Compensation
motor rated current will flow
Gain]
and trip at overload. Hunting or
oscillation.
• Torque at low speeds (10 Hz or
• E1-08 [Mid Point A Voltage]
lower) is not sufficient.
• E1-10 [Minimum Output
• Large initial vibration at start
up.
Speed precision is unsatisfactory.
C3-01 [Slip Compensation Gain]
*1
The default setting changes when the settings for C6-01 [Normal / Heavy Duty Selection] and o2-04 [Drive Model (KVA) Selection]
change.
*2
The default setting changes when the settings for A1-02 [Control Method Selection] and o2-04 change.
*3
The default setting changes when the settings for A1-02 and E1-03 [V/f Pattern Selection] change.
*4
Recommended settings are for 200 V class drives. Multiply the voltage by 2 for 400 V class drives.
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING

3.7 Fine Tuning during Test Runs (Adjust the Control Function)

Table 3.15 Parameters for Fine Tuning the Drive (A1-02 = 0 [V/f])
Parameter Number
Possible Solutions
• If torque is not sufficient with
heavy loads, decrease the
setting value.
• If hunting or oscillation occur
with light loads, increase the
setting value.
• If hunting occurs with a low-
inductance motor, for example a
motor with a larger frame size
or a high-frequency motor,
lower the setting value. Set n1-
01 = 1 [Hunting Prevention
Selection = Enabled].
• If the volume of the motor
excitation sound is too high,
increase the carrier frequency.
• If hunting or oscillation occur at
low or mid-range speeds,
decrease the carrier frequency.
• If torque or speed response are
slow, decrease the setting value.
• If hunting or oscillation occur,
increase the setting value.
• If torque at low speeds (10 Hz
or lower) is not sufficient,
increase the setting value.
• If hunting or oscillation occur
with light loads, decrease the
setting value.
Decrease the setting value in these
conditions:
• Drive trips at overload.
• Hunting or oscillation.
• If torque at low speeds (10 Hz
or lower) is not sufficient,
increase the setting value.
• If there is large initial vibration
Voltage]
at start up, decrease the setting
value
Set E2-01 [Motor Rated Current],
E2-02 [Motor Rated Slip], and E2-
03 [Motor No-Load Current], then
adjust C3-01.
Default
1.00
0.10 - 2.00
*1
1 (2 kHz)
1 to upper limit value
*2
200 ms
100 ms to 1000 ms
1.00
0.50 - 1.50
1.00
0.00 - 1.00
*3
• E1-08: 16.0 V
Default setting +/- 5 V
*3
• E1-10: 12.0 V
0.0 (no slip compensation)
0.5 - 1.5
Recommended Setting
*4
3
481

Advertisement

Table of Contents
loading

Table of Contents