Overview of Alarms
205005
<location>Cooling system: Cooling medium flow rate too low
Reaction:
NONE
Acknowledge:
NONE
Cause:
Cooling system: Alarm - flow rate has fallen below the alarm value
Remedy:
205050
<location>Parallel circuit configuration: Pulse enable in spite of pulse
inhibit
Reaction:
OFF2 (NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
A power module signals that the pulses are enabled although the pulses are inhibited.
Fault value (r0949, decimal):
Number of the power module involved.
Remedy:
The power module is defective and must be replaced.
205051
<location>Parallel circuit configuration: Power module pulse enable
missing
Reaction:
OFF2 (NONE, OFF1, OFF3, STOP1, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
For one or several power modules, the pulses were not able to be enabled.
Fault value (r0949, decimal):
Number of the power module involved.
Remedy:
- acknowledge power module faults that are still present.
- inhibit the pulses of the power module involved (p7001).
205052
<location>Parallel circuit configuration: Impermissible current
dissymmetry
Reaction:
NONE
Acknowledge:
NONE
Cause:
The deviation of the individual currents of the power modules exceeds the alarm threshold
specified in p7010.
Alarm value (r2124, decimal):
1: Phase U.
2: Phase V.
3. Phase W.
Remedy:
- inhibit the pulses of the faulted power module (p7001).
- check the connecting cables. Loose contacts can cause current spikes.
- the motor reactors are non-symmetrical or faulty and must be replaced.
- the CTs must be calibrated or replaced.
205053
<location>Parallel circuit configuration: Inadmissible DC link voltage
dissymmetry
Reaction:
NONE
Acknowledge:
NONE
Cause:
The deviation of the DC link voltage measured values exceeds the alarm threshold
specified in p7011.
Remedy:
- inhibit the pulses of the faulted power module (p7001).
- check the DC link connecting cables.
- the DC link voltage measurement is incorrect and must be calibrated or renewed.
205055
<location>Parallel circuit configuration: Power modules with different
code numbers
Reaction:
NONE
Acknowledge:
IMMEDIATELY
2-678
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
© Siemens AG, 2005. All rights reserved
08/2005