Siemens SINUMERIK 840D sl Series Diagnostics Manual page 884

Hide thumbs Also See for SINUMERIK 840D sl Series:
Table of Contents

Advertisement

Overview of Alarms
or MD 1141: $MD_MAGNETIZING_REACTANCE (magnetizing reactance) is less than or
equal to zero.
The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY
(channel not ready).
Reactions:
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
Remedy:
Please inform the authorized personnel/service department.
• For standard motors: Reset the drive (delete the bootfile) and repeat the startup.
• For third-party motors: Check and, if necessary, refer to the motor data sheet to correct
MD 1139: $MD_STATOR_LEAKAGE_REACTANCE (stator leakage reactance) or MD
1140: $MD_ROTOR_LEAKAGE_REACTANCE (rotor leakage reactance) or MD 1141:
$MD_MAGNETIZING_REACTANCE (magnetizing reactance).
Program Con-
Clear alarm with the RESET key in all channels. Restart part program.
tinuation:
300783
Axis %1 drive %2 rotor resistance invalid
Parameters:
%1 = NC axis number
%2 = Drive number
Definitions:
The value in drive MD 1138: $MD_ROTOR_COLD_RESISTANCE (cold rotor resistance)
is less than or equal to zero or a format overflow has occurred.
The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY
(channel not ready).
Reactions:
- NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
Remedy:
Please inform the authorized personnel/service department.
• For standard motors: Reset the drive (delete the bootfile) and repeat the startup.
• For third-party motors: One of the following machine data may contain an invalid value:
• Modify MD 1001: $MD_SPEEDCTRL_CYCLE_TIME (speed controller cycle)
• Modify MD 1134: $MD_MOTOR_NOMINAL_FREQUENCY (rated motor frequency)
• Modify MD 1138: $MD_ROTOR_COLD_RESISTANCE (cold rotor resistance)
• Modify MD 1139: $MD_STATOR_LEAKAGE_REACTANCE (Staenderstreureaktanz)
• Modify MD 1140: $MD_ROTOR_LEAKAGE_REACTANCE (rotor leakage reactance)
• Modify MD 1141: $MD_MAGNETIZING_REACTANCE (magnetizing reactance)
Fulfill the condition according to the folowing formula:
16 * P1001 * 0.00003125 * P1138 * 2PI * P1134 / (P1140 + P1141) < 1
Call the SIEMENS AG, SIMODRIVE Hotline.
Program Con-
Clear alarm with the RESET key in all channels. Restart part program.
tinuation:
2-884
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
© Siemens AG, 2005. All rights reserved
08/2005

Advertisement

Table of Contents
loading

Table of Contents