08/2005
202063
<location>Trace: Invalid data type
Reaction:
NONE
Acknowledge:
NONE
Cause:
The specified data type to select a signal using a physical address is invalid.
See also: p4711, p4730, p4731, p4732, p4733
Remedy:
Use a valid data type.
202070
<location>Trace: Parameter cannot be changed
Reaction:
NONE
Acknowledge:
NONE
Cause:
The trace parameter settings cannot be changed when the trace is active.
See also: p4700, p4710, p4711, p4712, p4713, p4714, p4715, p4716, p4720, p4721,
p4722, p4730, p4731, p4732, p4733, p4780, p4781, p4782, p4783, p4789, p4795
Remedy:
- stop the trace before parameterization.
- if required, start the trace.
202075
<location>Trace: Pretrigger time too long
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected pretrigger time must be shorter than the recording time.
See also: p4721, p4722
Remedy:
Check the pretrigger time setting and change if necessary.
202099
<location>Trace: Insufficient memory
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory space still available on the control unit is no longer sufficient for the trace
function.
Remedy:
Reduce the memory required, e.g. as follows:
- reduce the trace (record) time.
- increase the trace clock cycle.
- reduce the number of signals to be traced (recorded).
See also: r4708, r4799
202100
<location>CU: Computation deadtime current controller too low
Reaction:
NONE
Acknowledge:
NONE
Cause:
The value in p0118 produces a dead time of one clock cycle because it lies before the
setpoint becomes available. A possible cause could be, for example, that the system
characteristics no longer match those parameterized after a component has been
replaced.
Alarm value (r2134, floating point):
The minimum value for p0118 where a deadtime no longer occurs.
Remedy:
- set p0118 to a value greater than or equal to the alarm value.
- set p0117 to an automatic setting.
- check the firmware releases of the components involved.
See also: p0117, p0118
203500
<location>TM: Initialization
Reaction:
OFF1 (OFF2)
Acknowledge:
IMMEDIATELY (POWER ON)
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Overview of Alarms
2-675