Advertisement

Section 9
Control functions
9.4.4.4
642
shot pointer value increases. This is carried out until a successful reclosing or lockout
takes place after a complete shot sequence containing a total of five shots.
A070872 V1 EN
Figure 335:
Shot pointer function
Every time the shot pointer increases, the reclaim time starts. When the reclaim time
ends, the shot pointer sets to its initial value, unless no new shot is initiated. The shot
pointer increases when the reclose time elapses or at the falling edge of the
INC_SHOTP signal.
When SHOT_PTR has the value six, the AR function is in a so called pre-lockout state.
If a new initiation occurs during the pre-lockout state, the AR function goes to lockout.
Therefore, a new sequence initiation during the pre-lockout state is not possible.
The AR function goes to the pre-lockout state in the following cases:
During SOTF
When the AR function is active, it stays in a pre-lockout state for the time defined
by the reclaim time
When all five shots have been executed
When the frequent operation counter limit is reached. A new sequence initiation
forces the AR function to lockout.

Reclose controller

The reclose controller calculates the reclose, discrimination and reclaim times. The
reclose time is started when the INPRO signal is activated, that is, when the sequence
starts and the activated CBB defines the reclose time.
When the reclose time has elapsed, the CLOSE_CB output is not activated until the
following conditions are fulfilled:
1MRS758755 A
REC615 and RER615
Technical Manual