Signals - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
4.2.7.6
4.2.7.7
Table 387:
MFADPSDE Group settings (Basic)
Parameter
Values (Range)
Directional mode
Voltage start value
Operate delay time
Table 388:
MFADPSDE Group settings (Advanced)
Parameter
Values (Range)
Operating quantity
Min operate current
Tilt angle
REC615 and RER615
Technical Manual

Signals

Table 385:
MFADPSDE Input signals
Name
Io
Uo
BLOCK
RELEASE
RESET
Table 386:
MFADPSDE Output signals
Name
OPERATE
START
BLK_EF
INTR_EF
PEAK_IND
Settings
Unit
2=Forward
3=Reverse
0.01...1.00
xUn
60...1200000
ms
Unit
1=Adaptive
2=Amplitude
3=Resistive
0.005...5.000
xIn
2.0...20.0
deg
Type
Default
Description
SIGNAL
0
Residual current
SIGNAL
0
Residual voltage
BOOLEAN
0=False
Block signal for activating the blocking mode
BOOLEAN
0=False
External trigger to release neutral admittance
protection
BOOLEAN
0=False
External trigger to reset direction calculatio
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
BOOLEAN
Block signal for EF to indicate opposite direction
peaks
BOOLEAN
Intermittent earth-fault indication
BOOLEAN
Current transient detection indication
Step
Default
2=Forward
0.01
0.10
10
500
Step
Default
1=Adaptive
0.001
0.010
0.1
5.0
Section 4
Protection functions
Description
Directional mode
Voltage start value
Operate delay time
Description
Operating quantity selection
Minimum operate current
Characteristic tilt angle
393

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents