Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
Parameter
Time multiplier
Operating curve type
Operate delay time
Table 381:
WPWDE Non group settings (Basic)
Parameter
Operation
Table 382:
WPWDE Non group settings (Advanced)
Parameter
Measurement mode
Correction angle
Min operate current
Min operate voltage
Reset delay time
Pol reversal
Io signal Sel
Uo signal Sel
4.2.6.10
372
Values (Range)
Unit
0.05...2.00
5=ANSI Def. Time
15=IEC Def. Time
20=Wattmetric
IDMT
60...200000
ms
Values (Range)
Unit
1=on
5=off
Values (Range)
Unit
1=RMS
2=DFT
3=Peak-to-Peak
0.0...10.0
deg
0.010...1.000
xIn
0.01...1.00
xUn
0...60000
ms
0=False
1=True
1=Measured Io
2=Calculated Io
1=Measured Uo
2=Calculated Uo

Monitored data

Table 383:
WPWDE Monitored data
Name
FAULT_DIR
START_DUR
DIRECTION
ANGLE
Table continues on next page
Step
Default
0.01
1.00
15=IEC Def. Time
10
60
Step
Default
1=on
Step
Default
2=DFT
0.1
2.0
0.001
0.010
0.01
0.01
1
20
0=False
1=Measured Io
1=Measured Uo
Type
Values (Range)
Enum
0=unknown
1=forward
2=backward
3=both
FLOAT32
0.00...100.00
Enum
0=unknown
1=forward
2=backward
3=both
FLOAT32
-180.00...180.00
1MRS758755 A
Description
Time multiplier for Wattmetric IDMT
curves
Selection of time delay curve type
Operate delay time for definite time
Description
Operation Off / On
Description
Selects used current measurement mode
Angle correction
Minimum operating current
Minimum operating voltage
Reset delay time
Rotate polarizing quantity
Selection for used Io signal
Selection for used polarization signal
Unit
Description
Detected fault direction
%
Ratio of start time /
operate time
Direction information
deg
Angle between polarizing
and operating quantity
REC615 and RER615
Technical Manual