Configuration

The load profile record can be configured with the PCM600 tool or any tool
supporting the IEC 61850 standard.
The load profile record can be enabled or disabled with the Operation setting under the
Configuration/Load Profile Record menu.
Each protection relay can be mapped to each of the quantity channels of the load
profile record. The mapping is done with the Quantity selection setting of the
corresponding quantity channel.
The IP number of the protection relay and the content of the Bay name
setting are both included in the COMTRADE configuration file for
identification purposes.
The memory consumption of load profile record is supervised, and indicated with two
signals MEM_WARN and MEM_ALARM, which could be used to notify the customer that
recording should be backlogged by reading the recorded data from the protection
relay. The levels for MEM_WARN and MEM_ALARM are set by two parameters
Mem.warn level and Mem. Alarm level.

Signals

Table 194:
LDPRLRC Output signals
Name
Type
MEM_WARN
BOOLEAN
MEM_ALARM
BOOLEAN
Description
Recording memory warning status
Recording memory alarm status
1MRS758755 A
REC615 and RER615