1MRS758755 A
3.16.1.5
REC615 and RER615
Technical Manual
Functionality
NOT is used to generate combinatory expressions with Boolean variables.
NOT inverts the input signal.
Signals
Table 95:
NOT Input signal
Name
Type
I
BOOLEAN
Table 96:
NOT Output signal
Name
O
Settings
The function does not have any parameters available in LHMI or PCM600.

MAX3 function block

Function block
GUID-5454FE1C-2947-4337-AD58-39D266E91993 V1 EN
Figure 69:
Function block
Functionality
The maximum function MAX3 selects the maximum value from three analog values.
Disconnected inputs and inputs whose quality is bad are ignored. If all inputs are
disconnected or the quality is bad, MAX3 output value is set to -2^21.
Signals
Table 97:
MAX3 Input signals
Name
Type
IN1
FLOAT32
IN2
FLOAT32
IN3
FLOAT32
Default
0
Type
BOOLEAN
Default
0
0