Authorization; Audit Trail - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
2.4
2.4.1
REC615 and RER615
Technical Manual
Locally by connecting the laptop to the protection relay via the front
communication port.
Remotely over LAN/WAN.

Authorization

Four user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.
The default passwords in the protection relay delivered from the factory can be
changed with Administrator user rights.
User authorization is disabled by default for LHMI but WHMI always
uses authorization.
Table 3:
Predefined user categories
Username
VIEWER
OPERATOR
ENGINEER
ADMINISTRATOR
For user authorization for PCM600, see PCM600 documentation.

Audit trail

The protection relay offers a large set of event-logging functions. Critical system and
protection relay security-related events are logged to a separate nonvolatile audit trail
for the administrator.
REC615 and RER615 overview
User rights
Read only access
Selecting remote or local state with
Changing setting groups
Controlling
Clearing indications
Changing settings
Clearing event list
Clearing disturbance records
Changing system settings such as IP address, serial baud rate or
disturbance recorder settings
Setting the protection relay to test mode
Selecting language
All listed above
Changing password
Factory default activation
Section 2
(only locally)
35