Settings - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
4.5.1.7
Table 461:
FRPFRQ Group settings (Basic)
Parameter
Values (Range)
Operation mode
Start value Freq>
Start value Freq<
Start value df/dt
Operate Tm Freq
Operate Tm df/dt
Table 462:
FRPFRQ Non group settings (Basic)
Parameter
Values (Range)
Operation
Table 463:
FRPFRQ Non group settings (Advanced)
Parameter
Values (Range)
Reset delay Tm Freq
Reset delay Tm df/dt
4.5.1.8
REC615 and RER615
Technical Manual

Settings

Unit
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt
0.9000...1.2000
xFn
0.8000...1.1000
xFn
-0.2000...0.2000
xFn /s
80...200000
ms
120...200000
ms
Unit
1=on
5=off
Unit
0...60000
ms
0...60000
ms
Monitored data
Table 464:
FRPFRQ Monitored data
Name
START_DUR
ST_DUR_OFRQ
ST_DUR_UFRQ
ST_DUR_FRG
FRPFRQ
Step
Default
1=Freq<
0.0001
1.0500
0.0001
0.9500
0.0025
0.0100
10
200
10
400
Step
Default
1=on
Step
Default
1
0
1
0
Type
Values (Range)
FLOAT32
0.00...100.00
FLOAT32
0.00...100.00
FLOAT32
0.00...100.00
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Section 4
Protection functions
Description
Frequency protection operation mode
selection
Frequency start value overfrequency
Frequency start value underfrequency
Frequency start value rate of change
Operate delay time for frequency
Operate delay time for frequency rate of
change
Description
Operation Off / On
Description
Reset delay time for frequency
Reset delay time for rate of change
Unit
Description
%
Start duration
%
Start duration
%
Start duration
%
Start duration
Status
441