Signals - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
10.4.6
10.4.7
Table 704:
VSQVUB Non group settings (Basic)
Parameter
Values (Range)
Operation
Unb detection method
Unbalance start Val
Trigger mode
Percentile unbalance
Obs period selection
User Def Obs period
Obs period Str year
Table continues on next page
REC615 and RER615
Technical Manual

Signals

Table 702:
VSQVUB Input signals
Name
U_A
U_B
U_C
U
1
U
2
U
0
BLOCK
Table 703:
VSQVUB Output signals
Name
MN_UNB_AL
PCT_UNB_AL
OBS_PR_ACT
Settings
Unit
1=on
5=off
1=Neg Seq
2=Zero Seq
3=Neg to Pos Seq
4=Zero to Pos Seq
5=Ph vectors Comp
1...100
%
1=Single
2=Periodic
3=Continuous
1...100
%
1=1 Hour
2=12 Hours
3=1 Day
4=7 Days
5=User defined
1...168
h
2008...2076
Power quality measurement functions
Type
Default
Description
SIGNAL
0
Phase A voltage
SIGNAL
0
Phase B voltage
SIGNAL
0
Phase C voltage
SIGNAL
0
Positive phase sequence voltage
SIGNAL
0
Negative phase sequence voltage
SIGNAL
0
Zero sequence voltage
BOOLEAN
0=False
Block all outputs except measured values
Type
Description
BOOLEAN
Alarm active when 3 sec voltage unbalance
exceeds the limit
BOOLEAN
Alarm active when percentile unbalance exceeds
the limit
BOOLEAN
Observation period is active
Step
Default
1=on
3=Neg to Pos Seq
1
1
3=Continuous
1
95
5=User defined
1
168
2011
Section 10
Description
Operation On/Off
Set the operation mode for voltage
unbalance calculation
Voltage unbalance start value
Specifies the observation period
triggering mode
The percent to which percentile value
PCT_UNB_VAL is calculated
Observation period for unbalance
calculation
User define observation period for statistic
calculation
Calendar time for observation period start
year in YYYY
705