ABB RELION Series Technical Manual page 790

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 14
Technical data
784
Table 738:
Signal outputs and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
Minimum contact load
1) X100: IRF,SO2
Table 739:
Double-pole power outputs with TCS function X100: PO3 and PO4
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC (two
contacts connected in a series)
Minimum contact load
Trip-circuit monitoring (TCS)
Control voltage range
Current drain through the monitoring circuit
Minimum voltage over the TCS contact
Table 740:
Single-pole power output relays X100: PO1 and PO2
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R <40 ms, at 48/110/220 V DC
Minimum contact load
1)
Value
250 V AC/DC
5 A
10 A
15 A
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
Value
250 V AC/DC
8 A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
Value
250 V AC/DC
8 A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
REC615 and RER615
1MRS758755 A
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents