1MRS758755 A
5.4.9
5.4.10
REC615 and RER615
Technical Manual
Name
Type
A Flt Phs B Magn
FLOAT32
A Flt Phs B angle
FLOAT32
A Flt Phs C Magn
FLOAT32
A Flt Phs C angle
FLOAT32
V Flt Phs A Magn
FLOAT32
V Flt Phs A angle
FLOAT32
V Flt Phs B Magn
FLOAT32
V Flt Phs B angle
FLOAT32
V Flt Phs C Magn
FLOAT32
V Flt Phs C angle
FLOAT32

Technical data

Table 527:
SCEFRFLO Technical data
Characteristic
Measurement accuracy
Technical revision history
Table 528:
SCEFRFLO Technical revision history
Technical revision
B
Protection related functions
Values (Range)
Unit
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
-180.00...180.00
deg
0.00...40.00
xIn
-180.00...180.00
deg
Value
At the frequency f = f
Impedance:
±2.5% or ±0.25 Ω
Distance:
±2.5% or ±0.16 km/0.1 mile
XC0F_CALC:
±2.5% or ±50 Ω
IFLT_PER_ILD:
±5% or ±0.05
Change
Internal improvement.
Section 5
Description
Fault current phase B,
magnitude
Fault current phase B,
angle
Fault current phase C,
magnitude
Fault current phase C,
angle
Fault voltage phase A,
magnitude
Fault voltage phase A,
angle
Fault voltage phase B,
magnitude
Fault voltage phase B,
angle
Fault voltage phase C,
magnitude
Fault voltage phase C,
angle