Settings - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
8.2.5
REC615 and RER615
Technical Manual
The disturbance recorder follows the 1999 version of the
COMTRADE standard and uses the binary data file format.

Settings

Table 622:
RDRE Non-group general settings
Parameter
Values (Range) Unit
Operation
1=on
5=off
Record length
10...500
Pre-trg length
0...100
Operation
1=Saturation
mode
2=Overwrite
Exclusion time
0...1 000 000
Storage rate
32, 16, 8
Periodic trig
0...604 800
time
Stor. mode
0=Waveform
periodic
1=Trend /
cycle
Stor. mode
0=Waveform
manual
1=Trend /
cycle
Measurement functions
Step
1
fundamental
1
cycles
%
1
1
ms
1
samples per
fundamental
cycle
s
10
1
1
Section 8
Default
Description
1=on
Disturbance
recorder on/off
50
Size of the
recording in
fundamental
cycles
50
Length of the
recording
preceding the
triggering
1
Operation
mode of the
recorder
0
The time
during which
triggerings of
same type are
ignored
32
Storage rate
of the
waveform
recording
0
Time between
periodic
triggerings
0
Storage mode
for periodic
triggering
0
Storage mode
for manual
triggering
599