Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
8.1.7.5
8.1.7.6
8.1.7.7
REC615 and RER615
Technical Manual

Monitored data

Table 592:
RESVMMXU Monitored data
Name
Type
Uo-kV
FLOAT32
BLOCK
BOOLEAN
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
U_INST_RES
FLOAT32
U_ANGL_RES
FLOAT32
U_DB_RES
FLOAT32
U_DMD_RES
FLOAT32
U_RANGE_RES
Enum
Technical data
Table 593:
RESVMMXU Technical data
Characteristic
Operation accuracy
Suppression of harmonics
Technical revision history
Table 594:
RESVMMXU Technical revision history
Technical revision
B
C
D
E
Measurement functions
Values (Range)
Unit
0.00...4.00
xUn
0=False
1=True
0=False
1=True
0=False
1=True
0.00...4.00
xUn
-180.00...180.00
deg
0.00...4.00
xUn
0.00...4.00
xUn
0=normal
1=high
2=low
3=high-high
4=low-low
Value
Depending on the frequency of the measured
voltage: f/f
= ±2 Hz
n
±0.5% or ±0.002 × U
DFT: -50 dB at f = n × f
RMS: No suppression
Change
-
Residual voltage angle and demand value added
to Monitored data view
Internal improvement
Internal improvement
Section 8
Description
Measured residual
voltage
Block signal for all binary
outputs
High alarm
High warning
Residual voltage
Amplitude, magnitude of
instantaneous value
Residual voltage angle
Residual voltage
Amplitude, magnitude of
reported value
Demand value of residual
voltage
Residual voltage
Amplitude range
n
, where n = 2, 3, 4, 5,...
n
573