1MRS758755 A
Parameter
Values (Range)
Operating curve type
Operate delay time
Characteristic angle
Max forward angle
Max reverse angle
Min forward angle
Min reverse angle
Voltage start value
Table 342:
DEFHPDEF Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
Operation mode
Enable voltage limit
Table 343:
DEFHPDEF Non group settings (Basic)
Parameter
Values (Range)
Operation
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
REC615 and RER615
Technical Manual
Unit
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
15=IEC Def. Time
17=Programmable
40...200000
ms
-179...180
deg
0...180
deg
0...180
deg
0...180
deg
0...180
deg
0.010...1.000
xUn
Unit
1=Immediate
2=Def time reset
3=Inverse reset
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
0=False
1=True
Unit
1=on
5=off
0.0086...120.0000
0.0000...0.7120
0.02...2.00
0.46...30.00
0.0...1.0
Step
Default
15=IEC Def. Time
10
40
1
-90
1
80
1
80
1
80
1
80
0.001
0.010
Step
Default
1=Immediate
1=Phase angle
1=True
Step
Default
1=on
1
28.2000
1
0.1217
1
2.00
1
29.10
1
1.0
Section 4
Protection functions
Description
Selection of time delay curve type
Operate delay time
Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Voltage start value
Description
Selection of reset curve type
Operation criteria
Enable voltage limit
Description
Operation Off / On
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve