1MRS758755 A
Parameter
Values (Range)
Operate delay time
Characteristic angle
Max forward angle
Max reverse angle
Min forward angle
Min reverse angle
Voltage start value
Table 338:
FDEFLPDEF Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
Operation mode
Enable voltage limit
REC615 and RER615
Technical Manual
Unit
-23=Recloser E
(132)
-24=Recloser F
(163)
-25=Recloser G
(121)
-26=Recloser H
(122)
-27=Recloser J
(164)
-28=Recloser Kg
(165)
-29=Recloser Kp
(162)
-30=Recloser L
(107)
-31=Recloser M
(118)
-32=Recloser N
(104)
-33=Recloser P
(115)
-34=Recloser R
(105)
-35=Recloser T
(161)
-36=Recloser V
(137)
-37=Recloser W
(138)
-38=Recloser Y
(120)
-39=Recloser Z
(134)
50...200000
ms
-179...180
deg
0...180
deg
0...180
deg
0...180
deg
0...180
deg
0.010...1.000
xUn
Unit
1=Immediate
2=Def time reset
3=Inverse reset
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
0=False
1=True
Step
Default
10
50
1
-90
1
80
1
80
1
80
1
80
0.001
0.010
Step
Default
1=Immediate
1=Phase angle
1=True
Section 4
Protection functions
Description
Operate delay time
Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Voltage start value
Description
Selection of reset curve type
Operation criteria
Enable voltage limit
309