Signals; Analog Value Scaling Sca4Gapc; Function Block; Functionality - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
3.16.9.3
3.16.10
3.16.10.1
3.16.10.2
REC615 and RER615
Technical Manual

Signals

Table 158:
MVI4GAPC Input signals
Name
Type
IN1
INT32
IN2
INT32
IN3
INT32
IN4
INT32
Table 159:
MVI4GAPC Output signals
Name
Type
OUT1
INT32
OUT2
INT32
OUT3
INT32
OUT4
INT32

Analog value scaling SCA4GAPC

Function block

SCA4GAPC
AI1_VALUE
AO1_VALUE
AI2_VALUE
AO2_VALUE
AI3_VALUE
AO3_VALUE
AI4_VALUE
AO4_VALUE
GUID-9D830A50-37F1-4478-B458-9C90742ECA54 V1 EN
Figure 96:
Function block

Functionality

The analog value scaling function SCA4GAPC is used for scaling the analog value. It
allows creating events from analog values.
The analog value received via the AIn_VALUE input is scaled with the Scale ratio n
setting. The scaled value is available on the AOn_VALUE output.
Analog input range is from -10000.0 to 10000.0.
Default
Description
0
Integer input value 1
0
Integer input value 2
0
Integer input value 3
0
Integer input value 4
Description
Integer output value 1
Integer output value 2
Integer output value 3
Integer output value 4
Section 3
Basic functions
151