Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 6
Supervision functions
Parameter
Num of phases
V live value
V live time
V dead value
V dead time
Table 553:
PHSVPR Non group settings (Advanced)
Parameter
Relative hysteresis
6.4.8
6.4.9
534
Values (Range)
Unit
1=1 out of 3
2=2 out of 3
3=3 out of 3
0.2...1.0
xUn
40...10000
ms
0.1...0.8
xUn
40...10000
ms
Values (Range)
Unit
1.0...5.0
%

Monitored data

Table 554:
PHSVPR Monitored data
Name
PHSVPR
Technical data
Table 555:
PHSVPR Technical data
Characteristic
Operation accuracy
Operation time accuracy
Step
Default
1=1 out of 3
0.1
0.5
1
100
0.1
0.2
1
100
Step
Default
0.1
4.0
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
voltage: f
±1.5% of the set value or ±0.002 × U
±1.0% of the set value or ±20 ms
1MRS758755 A
Description
Number of phases required for voltage
supervision
Limit value for high voltage
Duration time for high voltage
Limit value for low voltage
Duration time for low voltage
Description
Relative hysteresis for voltage
supervision
Unit
Description
Status
±2 Hz
n
REC615 and RER615
Technical Manual
n

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents