1MRS758755 A
4.2.3.5
REC615 and RER615
Technical Manual
function is blocked and the timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the OPERATE output is not activated.

Application

INTRPTEF is an earth-fault function dedicated to operate in intermittent and
permanent earth faults occurring in distribution and sub-transmission networks. Fault
detection is done from the residual current and residual voltage signals by monitoring
the transients with predefined criteria. As the function has a dedicated purpose for the
fault types, fast detection and clearance of the faults can be achieved.
Intermittent earth fault
Intermittent earth fault is a special type of fault that is encountered especially in
compensated networks with underground cables. A typical reason for this type of fault
is the deterioration of cable insulation either due to mechanical stress or due to
insulation material aging process where water or moisture gradually penetrates the
cable insulation. This eventually reduces the voltage withstand of the insulation,
leading to a series of cable insulation breakdowns. The fault is initiated as the phase-
to-earth voltage exceeds the reduced insulation level of the fault point and mostly
extinguishes itself as the fault current drops to zero for the first time, as shown in
Figure
163. As a result, very short transients, that is, rapid changes in the form of
spikes in residual current (Io) and in residual voltage (Uo), can be repeatedly
measured. Typically, the fault resistance in case of an intermittent earth fault is only
a few ohms.
Residual current Io and residual voltage Uo
COMP. COIL
R e
R e
K
K
FEEDER MEAS
FEEDER
INCOMER
I
Iov
Ioj
ctot
Fault
U tres
Point
U tres
GUID-415078AD-21B3-4103-9622-712BB88F274A V2 EN
Figure 163:
Typical intermittent earth-fault characteristics
Iov
(Healthy
Feeder)
0.1
0
Uo
-0.1
-0.2
R
Ioj
f
-0.3
Section 4
Protection functions
Uo
Pulse width
400 - 800 s
Pulse interval
5 - 300 ms
(Faulty
Feeder)
Peak value
~0.1 ... 5 kA
321