ABB RELION Series Technical Manual page 314

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
Parameter
Operating curve type
Table continues on next page
308
Values (Range)
Unit
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
-1=Recloser 1
(102)
-2=Recloser 2
(135)
-3=Recloser 3
(140)
-4=Recloser 4
(106)
-5=Recloser 5
(114)
-6=Recloser 6
(136)
-7=Recloser 7
(152)
-8=Recloser 8
(113)
-9=Recloser
8+ (111)
-10=Recloser 8*
-11=Recloser 9
(131)
-12=Recloser 11
(141)
-13=Recloser 13
(142)
-14=Recloser 14
(119)
-15=Recloser 15
(112)
-16=Recloser 16
(139)
-17=Recloser 17
(103)
-18=Recloser 18
(151)
-19=Recloser A
(101)
-20=Recloser B
(117)
-21=Recloser C
(133)
-22=Recloser D
(116)
Step
Default
15=IEC Def. Time
1MRS758755 A
Description
Selection of time delay curve type
REC615 and RER615
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents