Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
Table 389:
MFADPSDE Non group settings (Basic)
Parameter
Operation
Operation mode
Table 390:
MFADPSDE Non group settings (Advanced)
Parameter
Io signal Sel
Uo signal Sel
Peak counter limit
Start delay time
Reset delay time
Pol reversal
4.2.7.8
394
Values (Range)
Unit
1=on
5=off
1=Intermittent EF
3=General EF
4=Alarming EF
Values (Range)
Unit
1=Measured Io
2=Calculated Io
1=Measured Uo
2=Calculated Uo
2...20
30...60000
ms
0...60000
ms
0=False
1=True

Monitored data

Table 391:
MFADPSDE Monitored data
Name
START_DUR
FAULT_DIR
DIRECTION
ANGLE
MFADPSDE
Step
Default
1=on
3=General EF
Step
Default
1=Measured Io
1=Measured Uo
1
2
1
30
1
500
0=False
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
0=unknown
1=forward
2=backward
3=both
Enum
0=unknown
1=forward
2=backward
3=both
FLOAT32
-180.00...180.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS758755 A
Description
Operation Off / On
Operation criteria
Description
Selection for used Io signal
Selection for used Uo signal
Peak counter limit for restriking EF
Start delay time
Reset delay time
Rotate polarizing quantity
Unit
Description
%
Ratio of start time /
operate time
Detected fault direction
Direction information
deg
Angle between polarizing
and operating quantity
Status
REC615 and RER615
Technical Manual