Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
Parameter
Curve parameter D
Curve parameter E
Num of start phases
Table 261:
DPHHPDOC Non group settings (Advanced)
Parameter
Reset delay time
Minimum operate time
Allow Non Dir
Measurement mode
Min operate current
Min operate voltage
4.1.2.10
248
Values (Range)
Unit
0.46...30.00
0.0...1.0
1=1 out of 3
2=2 out of 3
3=3 out of 3
Values (Range)
Unit
0...60000
ms
20...60000
ms
0=False
1=True
1=RMS
2=DFT
3=Peak-to-Peak
0.01...1.00
xIn
0.01...1.00
xUn

Monitored data

Table 262:
FDPHLPDOC Monitored data
Name
START_DUR
FAULT_DIR
DIRECTION
DIR_A
DIR_B
DIR_C
ANGLE_A
Table continues on next page
Step
Default
1
29.10
1
1.0
1=1 out of 3
Step
Default
1
20
1
20
0=False
2=DFT
0.01
0.01
0.01
0.01
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
0=unknown
1=forward
2=backward
3=both
Enum
0=unknown
1=forward
2=backward
3=both
Enum
0=unknown
1=forward
2=backward
-1=both
Enum
0=unknown
1=forward
2=backward
-1=both
Enum
0=unknown
1=forward
2=backward
-1=both
FLOAT32
-180.00...180.00
1MRS758755 A
Description
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Number of phases required for operate
activation
Description
Reset delay time
Minimum operate time for IDMT curves
Allows prot activation as non-dir when dir
info is invalid
Selects used measurement mode
Minimum operating current
Minimum operating voltage
Unit
Description
%
Ratio of start time /
operate time
Detected fault direction
Direction information
Direction phase A
Direction phase B
Direction phase C
deg
Calculated angle
difference, Phase A
REC615 and RER615
Technical Manual