Application Configuration And Test Mode; Control Mode - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
3.6.3
3.6.4
REC615 and RER615
Technical Manual
Table 19:
Test mode
Test mode
Description
Normal mode
Normal operation
IED blocked
Protection working as in "Normal mode" but ACT
configuration can be used to block physical
outputs to process. Control function commands
blocked.
IED test
Protection working as in "Normal mode" but
protection functions are working in parallel with
test parameters.
IED test and blocked
Protection working as in "Normal mode" but
protection functions are working in parallel with
test parameters. ACT configuration can be used to
block physical outputs to process. Control function
commands blocked.
Behavior data objects in all logical nodes follow LD0.LLN0.Mod
value. If "Normal mode" is selected, behaviour data objects follow
mode (.Mod) data object of the corresponding logical device.
Vertical and horizontal communication is not blocked by the "IED
blocked" or "IED test and blocked" modes.

Application configuration and Test mode

The physical outputs from control commands to process are blocked with "IED
blocked" and "IED test and blocked" modes. If physical outputs need to be blocked
from the protection, the application configuration must be used to block these signals.
Blocking scheme needs to use BEH_BLK output of PROTECTION function block.

Control mode

The mode of all logical nodes located under CTRL logical device can be set with
Control mode. The Control mode parameter is available via the HMI or PCM600 path
Configuration/Control/General. By default, Control mode can only be set locally
through LHMI.Control mode inherits its value from Test mode but Control
mode "On", "Blocked" and "Off" can also be set independently. Control mode is also
available via IEC 61850 communication (CTRL.LLN0.Mod).
Table 20:
Control mode
Control mode
On
Blocked
Off
Description
Normal operation
Control function commands blocked
Control functions disabled
Section 3
Basic functions
Protection BEH_BLK
FALSE
TRUE
FALSE
TRUE
Control BEH_BLK
FALSE
TRUE
FALSE
63