Technical Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.4.4.9
4.4.4.10
4.4.5
4.4.5.1
430

Technical data

Table 446:
NSPTOV Technical data
Characteristic
Operation accuracy
1)2)
Start time
U
value
U
value
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Suppression of harmonics
1) Negative-sequence voltage before fault = 0.0 × U
nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
Technical revision history
Table 447:
NSPTOV Technical revision history
Technical revision
B
C
D
Positive-sequence undervoltage protection PSPTUV
Identification
Function description
Positive-sequence undervoltage
protection
Value
Depending on the frequency of the voltage
measured: f
±1.5% of the set value or ±0.002 × U
Minimum
Start
= 1.1 × set
33 ms
Fault
24 ms
= 2.0 × set
Start
Fault
Typically 40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
DFT: -50 dB at f = n × f
, f
= 50 Hz, negative-sequence overvoltage with
n
n
Change
Internal change
Internal improvement.
Internal improvement.
IEC 61850
identification
PSPTUV
1MRS758755 A
n
n
Typical
Maximum
35 ms
37 ms
26 ms
28 ms
, where n = 2, 3, 4, 5,...
n
IEC 60617
ANSI/IEEE C37.2
identification
device number
U1<
47U+
REC615 and RER615
Technical Manual