Signals; Settings - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.13.3.4
3.13.3.5
Table 48:
ULTVTR Non group settings (Basic)
Parameter
Primary voltage
Secondary voltage
VT connection
Amplitude Corr A
Amplitude Corr B
Amplitude Corr C
Division ratio
Voltage input type
Angle Corr A
Angle Corr B
Angle Corr C
104

Signals

Table 46:
ULTVTR Input signals
Name
UL1
UL2
UL3
MINCB_OPEN
Table 47:
ULTVTR Output signals
Name
ALARM
WARNING

Settings

Values (Range)
Unit
0.100...440.000
kV
60...210
V
1=Wye
2=Delta
3=U12
4=UL1
0.9000...1.1000
0.9000...1.1000
0.9000...1.1000
1000...20000
1=Voltage trafo
3=CVD sensor
-20.0000...20.0000
deg
-20.0000...20.0000
deg
-20.0000...20.0000
deg
Type
Default
Description
INT32-UL1
0
IEC61850-9-2 phase 1 voltage
INT32-UL2
0
IEC61850-9-2 phase 2 voltage
INT32-UL3
0
IEC61850-9-2 phase 3 voltage
BOOLEAN
0=False
Active when external MCB opens protected voltage
circuit
Type
Description
BOOLEAN
Alarm
BOOLEAN
Warning
Step
Default
0.001
20.000
1
100
2=Delta
0.0001
1.0000
0.0001
1.0000
0.0001
1.0000
1
10000
1=Voltage trafo
0.0001
0.0000
0.0001
0.0000
0.0001
0.0000
1MRS758755 A
Description
Primary rated voltage
Secondary rated voltage
Voltage transducer measurement
connection
Phase A Voltage phasor magnitude
correction of an external voltage
transformer
Phase B Voltage phasor magnitude
correction of an external voltage
transformer
Phase C Voltage phasor magnitude
correction of an external voltage
transformer
Voltage sensor division ratio
Type of the voltage input
Phase A Voltage phasor angle correction
of an external voltage transformer
Phase B Voltage phasor angle correction
of an external voltage transformer
Phase C Voltage phasor angle correction
of an external voltage transformer
REC615 and RER615
Technical Manual