Technical Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
9.4.10
9.4.11
9.5
9.5.1
REC615 and RER615
Technical Manual
Name
Type
MAN_CB_CL
BOOLEAN
SOTF
BOOLEAN
DARREC
Enum

Technical data

Table 672:
DARREC Technical data
Characteristic
Operate time accuracy
Technical revision history
Table 673:
DARREC Technical revision history
Technical revision
B
C
D
E
F
Automatic transfer switch ATSABTC
Identification
Description
Automatic transfer switch
Values (Range)
Unit
0=False
1=True
0=False
1=True
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
±1.0% of the set value or ±20 ms
Change
The PROT_DISA output removed and removed
the related settings
The default value of the
setting changed from "True" to "False"
SHOT_PTR output range 0...7 (earlier 0...6)
Monitored data ACTIVE transferred to be ACT
visible output. SHOT_PTR output range 1...7.
Internal improvement
IEC 61850
identification
ATSABTC
Section 9
Control functions
Description
Indicates CB manual
closing during reclosing
sequence
Switch-onto-fault
Status
CB closed Pos status
IEC 60617
ANSI/IEEE
identification
C37.2 device
number
ATSABTC
ATSABTC
665