REC615 and RER615
Technical Manual

Local/remote control function block CONTROL

Function block

GUID-FA386432-3AEF-468D-B25E-D1C5BDA838E3 V3 EN
Figure 97:
Function block

Functionality

Local/Remote control is by default realized through the R/L button on the front panel.
The control via binary input can be enabled by setting the value of the LR control
setting to "Binary input". The binary input control requires that the CONTROL
function is instantiated in the product configuration.
Local/Remote control supports multilevel access for control operations in substations
according to the IEC 61850 standard. Multilevel control access with separate station
control access level is not supported by other protocols than IEC 61850.
The actual Local/Remote control state is evaluated by the priority scheme on the
function block inputs. If more than one input is active, the input with the highest
priority is selected. The priority order is "off", "local", "station", "remote", "all".
The actual state is reflected on the CONTROL function outputs. Only one output is
active at a time.
Table 163:
Truth table for CONTROL
CTRL_OFF
CTRL_LOC
TRUE
N/A
FALSE
TRUE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
Input
CTRL_STA
CTRL_REM
N/A
N/A
N/A
N/A
TRUE
N/A
FALSE
TRUE
FALSE
FALSE
FALSE
FALSE
Section 3
Basic functions
Output
CTRL_ALL
N/A
OFF = TRUE
N/A
LOCAL =
TRUE
N/A
STATION =
TRUE
TRUE
REMOTE =
TRUE
TRUE
ALL = TRUE
FALSE
OFF = TRUE
153