Section 3
Basic functions
3.19.2.3
3.19.2.4
198
Signals
Table 199:
SCHLCCH1 output signals
Parameter
Values (Range) Unit
CH1LIV
True
False
LNK1LIV
Up
Down
Table 200:
SCHLCCH2 output signals
Parameter
Values (Range) Unit
CH2LIV
True
False
LNK2LIV
Up
Down
Table 201:
SCHLCCH3 output signals
Parameter
Values (Range) Unit
CH3LIV
True
False
LNK3LIV
Up
Down
Settings
Table 202:
Port mode settings
Parameter
Values (Range) Unit
Port 1 Mode
Off
On
Port 2 Mode
Off
On
Port 3 Mode
Off
On
Step
Default
Description
Status of Ethernet channel X1/LAN.
Value is "True" if the port is receiving
Ethernet frames. Valid only when
Redundant mode is set to "None" or port
is not one of the redundant ports (LAN A
or LAN B).
Link status of Ethernet port X1/LAN.
Step
Default
Description
Status of Ethernet channel X2/LAN.
Value is "True" if the port is receiving
Ethernet frames. Valid only when
Redundant mode is set to "None" or port
is not one of the redundant ports (LAN A
or LAN B).
Link status of Ethernet port X2/LAN.
Step
Default
Description
Status of Ethernet channel X3/LAN.
Value is "True" if the port is receiving
Ethernet frames. Valid only when
Redundant mode is set to "None" or port
is not one of the redundant ports (LAN A
or LAN B).
Link status of Ethernet port X3/LAN.
Step
Default Description
On
Mode selection for rear port(s). If port is
not used, it can be set to "Off".
On
Mode selection for rear port(s). If port is
not used, it can be set to "Off". Port
cannot be set to "Off" when
mode is "HSR" or "PRP" and port is one
of the redundant ports (LAN A or LAN B).
On
Mode selection for rear port(s). If port is
not used, it can be set to "Off". Port
cannot be set to "Off" when
mode is "HSR" or "PRP" and port is one
of the redundant ports (LAN A or LAN B).
1MRS758755 A
Redundant
Redundant
REC615 and RER615