Table 749:
Mechanical tests
Description
Vibration tests (sinusoidal)
Shock and bump test
Seismic test
Table 750:
Environmental tests
Description
Dry heat test
Cold test
Damp heat test
Change of temperature test
Storage test
1) For relays with an LC communication interface the maximum operating temperature is +70
Table 751:
Product safety
Description
LV directive
Standard
Table 752:
EMC compliance
Description
EMC directive
Standard
Protection relay and functionality tests
Requirement
Class 2
Class 2
Class 2
Type test value
96 h at +55ºC
1)
16 h at +85ºC
96 h at -25ºC
16 h at -40ºC
6 cycles (12 h + 12 h) at
+25°C...+55°C, humidity
>93%
5 cycles (3 h + 3 h)
at -25°C...+55°C
96 h at -40ºC
96 h at +85ºC
Reference
2006/95/EC
EN 60255-27 (2013)
EN 60255-1 (2009)
Reference
2004/108/EC
EN 60255-26 (2013)
Section 15
Reference
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
IEC 60255-21-3
Reference
IEC 60068-2-2
IEC 60068-2-1
IEC 60068-2-30
IEC60068-2-14
IEC 60068-2-1
IEC 60068-2-2
o
C
789