1MRS758755 A
REC615 and RER615
Technical Manual
Table 735:
Energizing inputs of SIM0002/SIM0904
Description
Current sensor input
Rated current voltage (in
secondary side)
Continuous voltage
withstand
Input impedance at 50/60
Hz
Voltage sensor input
Rated voltage
Continuous voltage
withstand
Input impedance at 50/60
Hz
1) Equals the current range of 40...4000 A with a 80 A, 3 mV/Hz Rogowski
2) Depending on the used nominal current (hardware gain)
3) This range is covered (up to 2*rated) with sensor division ratio of 10 000:1
Table 736:
Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption
Threshold voltage
Reaction time
Table 737:
Signal output with high make and carry
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R <40 ms
Minimum contact load
1) X100: SO1
X110: SO1, SO2
X130: SO1, SO2 when REC615 is equipped with BIO0006
Technical data
Value
1)
75 mV...9000 mV
125 V
2)
2...3 MΩ
3)
6 kV...30 kV
50 V
3 MΩ
Value
±20% of the rated voltage
24...250 V DC
1.6...1.9 mA
31.0...570.0 mW
16...176 V DC
3 ms
1)
Value
250 V AC/DC
5 A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
Section 14
783