1MRS758755 A
4.1.1.7
REC615 and RER615
Technical Manual
Operating curve type
(-32)=Recloser N (104)
(-33)=Recloser P (115)
(-34)=Recloser R (105)
(-35)=Recloser T (161)
(-36)=Recloser V (137)
(-37)=Recloser W (138)
(-38)=Recloser Y (120)
(-39)=Recloser Z (134)
PHIPTOC supports only definite time characteristic.
For a detailed description of timers, see the
features
Table 205:
Reset time characteristics supported by different stages
Reset curve type
(F)PHLPTOC
(1) Immediate
(2) Def time reset
(3) Inverse reset
The Type of reset curve setting does not apply to PHIPTOC or when
the DT operation is selected. The reset is purely defined by the Reset
delay time setting.

Application

(F)PHxPTOC is used in several applications in the power system. The applications
include but are not limited to:
Selective overcurrent and short-circuit protection of feeders in distribution and
subtransmission systems
Backup overcurrent and short-circuit protection of power transformers and
generators
Overcurrent and short-circuit protection of various devices connected to the
power system, for example shunt capacitor banks, shunt reactors and motors
General backup protection
section in this manual.
PHHPTOC
x
x
x
x
x
x
Section 4
Protection functions
(F)PHLPTOC
PHHPTOC
x
x
x
x
x
x
x
x
General function block
Note
Available for all operate time curves
Available for all operate time curves
Available only for ANSI and user
programmable curves